Supercooling degree is one of the important parameters for evaluating the operating status of a refrigeration system. Its main function is to ensure that there is sufficient liquid refrigerant at the inlet of the throttling device, reducing the occurrence of flashing gas in the pipeline before throttling, and providing a more stable supply of liquid refrigerant to the evaporator.
I. Calculation formula and measurement method of supercooling degree
Calculation formula of supercooling degree:
Supercooling degree = Condensation saturation temperature - Actual temperature of liquid refrigerant
Condensation saturation temperature: Measure the pressure on the high-pressure side of the system, and convert it to the saturation temperature under the corresponding pressure-temperature table of the refrigerant.
Actual temperature of the liquid pipe: Use a contact-type temperature probe to measure the actual temperature of the liquid pipe at the outlet of the condenser.
When measuring on-site, the following points should be noted: The pressure measurement point should be as close as possible to the outlet of the condenser, and the temperature measurement point should also be selected at the corresponding position to avoid calculation deviations caused by pipeline pressure drop and temperature rise.
The temperature probe should be tightly attached to the clean copper pipe surface, insulated well, and reduce the influence of environmental temperature on the measurement result.
When measuring, try to avoid directly using an infrared thermometer to measure the surface of the copper pipe, because the metal surface has a low emissivity and is prone to measurement errors.
For non-azeotropic mixed refrigerants such as R410A, when calculating supercooling degree, the bubble point temperature should be used instead of the dew point temperature.
II. Reference range and influencing factors of supercooling degree
Different refrigeration equipment, refrigerants, condenser structures, and operating conditions have different requirements for supercooling degree. A fixed value cannot be used to judge all units.
The common reference range on-site is as follows:
Air-cooled refrigeration units: Usually about 3 to 8℃.
Water-cooled refrigeration units: Usually about 3 to 8℃.
Low-temperature units with economizers: The supercooling degree may reach 8 to 15℃, depending on the structure and design parameters of the economizer.
These values are used for on-site preliminary judgment. In practice, they should be based on the technical data and design operating parameters of the equipment manufacturer. Supercooling degree is not necessarily the higher the better.
Appropriate increase in supercooling degree can increase the refrigeration capacity per unit mass of refrigerant, reduce the flashing gas in the pipeline, and improve the system operating efficiency. However, if the supercooling degree is abnormally high, it may indicate liquid accumulation in the system, unreasonable refrigerant charging, or abnormal measurement of condensing pressure and liquid pipe temperature, and it is necessary to combine other operating parameters for comprehensive judgment.